Meters
Point names are the ones records use; [*] stands for a repeating group's index. See Supported SunSpec models for every group.
| Model | Name in records | Points |
|---|---|---|
| 201 | ac_meter_an_or_ab | 62 |
| 202 | ac_meter_abn | 62 |
| 203 | ac_meter_abcn | 62 |
| 204 | ac_meter_abc | 62 |
| 211 | ac_meter_an_or_ab_float | 62 |
| 212 | ac_meter_abn_float | 62 |
| 213 | ac_meter_abcn_float | 62 |
| 214 | ac_meter_abc_float | 62 |
| 220 | ac_meter_secure | 22 |
Model 201: Meter (Single Phase) single phase (AN or AB) meter
Name in records: ac_meter_an_or_ab.
Include this model for single phase (AN or AB) metering
| Point | Type | Units | Label | Description |
|---|---|---|---|---|
A | int16 | A | Amps | Total AC Current |
AphA | int16 | A | Amps PhaseA | Phase A Current |
AphB | int16 | A | Amps PhaseB | Phase B Current |
AphC | int16 | A | Amps PhaseC | Phase C Current |
PhV | int16 | V | Voltage LN | Line to Neutral AC Voltage (average of active phases) |
PhVphA | int16 | V | Phase Voltage AN | Phase Voltage AN |
PhVphB | int16 | V | Phase Voltage BN | Phase Voltage BN |
PhVphC | int16 | V | Phase Voltage CN | Phase Voltage CN |
PPV | int16 | V | Voltage LL | Line to Line AC Voltage (average of active phases) |
PPVphAB | int16 | V | Phase Voltage AB | Phase Voltage AB |
PPVphBC | int16 | V | Phase Voltage BC | Phase Voltage BC |
PPVphCA | int16 | V | Phase Voltage CA | Phase Voltage CA |
Hz | int16 | Hz | Hz | Frequency |
W | int16 | W | Watts | Total Real Power |
WphA | int16 | W | Watts phase A | |
WphB | int16 | W | Watts phase B | |
WphC | int16 | W | Watts phase C | |
VA | int16 | VA | VA | AC Apparent Power |
VAphA | int16 | VA | VA phase A | |
VAphB | int16 | VA | VA phase B | |
VAphC | int16 | VA | VA phase C | |
VAR | int16 | var | VAR | Reactive Power |
VARphA | int16 | var | VAR phase A | |
VARphB | int16 | var | VAR phase B | |
VARphC | int16 | var | VAR phase C | |
PF | int16 | Pct | PF | Power Factor |
PFphA | int16 | Pct | PF phase A | |
PFphB | int16 | Pct | PF phase B | |
PFphC | int16 | Pct | PF phase C | |
TotWhExp | acc32 | Wh | Total Watt-hours Exported | Total Real Energy Exported |
TotWhExpPhA | acc32 | Wh | Total Watt-hours Exported phase A | |
TotWhExpPhB | acc32 | Wh | Total Watt-hours Exported phase B | |
TotWhExpPhC | acc32 | Wh | Total Watt-hours Exported phase C | |
TotWhImp | acc32 | Wh | Total Watt-hours Imported | Total Real Energy Imported |
TotWhImpPhA | acc32 | Wh | Total Watt-hours Imported phase A | |
TotWhImpPhB | acc32 | Wh | Total Watt-hours Imported phase B | |
TotWhImpPhC | acc32 | Wh | Total Watt-hours Imported phase C | |
TotVAhExp | acc32 | VAh | Total VA-hours Exported | Total Apparent Energy Exported |
TotVAhExpPhA | acc32 | VAh | Total VA-hours Exported phase A | |
TotVAhExpPhB | acc32 | VAh | Total VA-hours Exported phase B | |
TotVAhExpPhC | acc32 | VAh | Total VA-hours Exported phase C | |
TotVAhImp | acc32 | VAh | Total VA-hours Imported | Total Apparent Energy Imported |
TotVAhImpPhA | acc32 | VAh | Total VA-hours Imported phase A | |
TotVAhImpPhB | acc32 | VAh | Total VA-hours Imported phase B | |
TotVAhImpPhC | acc32 | VAh | Total VA-hours Imported phase C | |
TotVArhImpQ1 | acc32 | varh | Total VAR-hours Imported Q1 | Total Reactive Energy Imported Quadrant 1 |
TotVArhImpQ1PhA | acc32 | varh | Total VAr-hours Imported Q1 phase A | |
TotVArhImpQ1PhB | acc32 | varh | Total VAr-hours Imported Q1 phase B | |
TotVArhImpQ1PhC | acc32 | varh | Total VAr-hours Imported Q1 phase C | |
TotVArhImpQ2 | acc32 | varh | Total VAr-hours Imported Q2 | Total Reactive Power Imported Quadrant 2 |
TotVArhImpQ2PhA | acc32 | varh | Total VAr-hours Imported Q2 phase A | |
TotVArhImpQ2PhB | acc32 | varh | Total VAr-hours Imported Q2 phase B | |
TotVArhImpQ2PhC | acc32 | varh | Total VAr-hours Imported Q2 phase C | |
TotVArhExpQ3 | acc32 | varh | Total VAr-hours Exported Q3 | Total Reactive Power Exported Quadrant 3 |
TotVArhExpQ3PhA | acc32 | varh | Total VAr-hours Exported Q3 phase A | |
TotVArhExpQ3PhB | acc32 | varh | Total VAr-hours Exported Q3 phase B | |
TotVArhExpQ3PhC | acc32 | varh | Total VAr-hours Exported Q3 phase C | |
TotVArhExpQ4 | acc32 | varh | Total VAr-hours Exported Q4 | Total Reactive Power Exported Quadrant 4 |
TotVArhExpQ4PhA | acc32 | varh | Total VAr-hours Exported Q4 Imported phase A | |
TotVArhExpQ4PhB | acc32 | varh | Total VAr-hours Exported Q4 Imported phase B | |
TotVArhExpQ4PhC | acc32 | varh | Total VAr-hours Exported Q4 Imported phase C | |
Evt | bitfield32 | Events | Meter Event Flags |
Value names:
Evt(bitfield32): bit 2Power_Failure, bit 3Under_Voltage, bit 4Low_PF, bit 5Over_Current, bit 6Over_Voltage, bit 7Missing_Sensor, bit 16OEM01, bit 17OEM02, bit 18OEM03, bit 19OEM04, bit 20OEM05, bit 21OEM06, bit 22OEM07, bit 23OEM08, bit 24OEM09, bit 25OEM10, bit 26OEM11, bit 27OEM12, bit 28OEM13, bit 29OEM14, bit 30OEM15
Model 202: split single phase (ABN) meter
Name in records: ac_meter_abn.
| Point | Type | Units | Label | Description |
|---|---|---|---|---|
A | int16 | A | Amps | Total AC Current |
AphA | int16 | A | Amps PhaseA | Phase A Current |
AphB | int16 | A | Amps PhaseB | Phase B Current |
AphC | int16 | A | Amps PhaseC | Phase C Current |
PhV | int16 | V | Voltage LN | Line to Neutral AC Voltage (average of active phases) |
PhVphA | int16 | V | Phase Voltage AN | Phase Voltage AN |
PhVphB | int16 | V | Phase Voltage BN | Phase Voltage BN |
PhVphC | int16 | V | Phase Voltage CN | Phase Voltage CN |
PPV | int16 | V | Voltage LL | Line to Line AC Voltage (average of active phases) |
PhVphAB | int16 | V | Phase Voltage AB | Phase Voltage AB |
PhVphBC | int16 | V | Phase Voltage BC | Phase Voltage BC |
PhVphCA | int16 | V | Phase Voltage CA | Phase Voltage CA |
Hz | int16 | Hz | Hz | Frequency |
W | int16 | W | Watts | Total Real Power |
WphA | int16 | W | Watts phase A | |
WphB | int16 | W | Watts phase B | |
WphC | int16 | W | Watts phase C | |
VA | int16 | VA | VA | AC Apparent Power |
VAphA | int16 | VA | VA phase A | |
VAphB | int16 | VA | VA phase B | |
VAphC | int16 | VA | VA phase C | |
VAR | int16 | var | VAR | Reactive Power |
VARphA | int16 | var | VAR phase A | |
VARphB | int16 | var | VAR phase B | |
VARphC | int16 | var | VAR phase C | |
PF | int16 | Pct | PF | Power Factor |
PFphA | int16 | Pct | PF phase A | |
PFphB | int16 | Pct | PF phase B | |
PFphC | int16 | Pct | PF phase C | |
TotWhExp | acc32 | Wh | Total Watt-hours Exported | Total Real Energy Exported |
TotWhExpPhA | acc32 | Wh | Total Watt-hours Exported phase A | |
TotWhExpPhB | acc32 | Wh | Total Watt-hours Exported phase B | |
TotWhExpPhC | acc32 | Wh | Total Watt-hours Exported phase C | |
TotWhImp | acc32 | Wh | Total Watt-hours Imported | Total Real Energy Imported |
TotWhImpPhA | acc32 | Wh | Total Watt-hours Imported phase A | |
TotWhImpPhB | acc32 | Wh | Total Watt-hours Imported phase B | |
TotWhImpPhC | acc32 | Wh | Total Watt-hours Imported phase C | |
TotVAhExp | acc32 | VAh | Total VA-hours Exported | Total Apparent Energy Exported |
TotVAhExpPhA | acc32 | VAh | Total VA-hours Exported phase A | |
TotVAhExpPhB | acc32 | VAh | Total VA-hours Exported phase B | |
TotVAhExpPhC | acc32 | VAh | Total VA-hours Exported phase C | |
TotVAhImp | acc32 | VAh | Total VA-hours Imported | Total Apparent Energy Imported |
TotVAhImpPhA | acc32 | VAh | Total VA-hours Imported phase A | |
TotVAhImpPhB | acc32 | VAh | Total VA-hours Imported phase B | |
TotVAhImpPhC | acc32 | VAh | Total VA-hours Imported phase C | |
TotVArhImpQ1 | acc32 | varh | Total VAR-hours Imported Q1 | Total Reactive Energy Imported Quadrant 1 |
TotVArhImpQ1PhA | acc32 | varh | Total VAr-hours Imported Q1 phase A | |
TotVArhImpQ1PhB | acc32 | varh | Total VAr-hours Imported Q1 phase B | |
TotVArhImpQ1PhC | acc32 | varh | Total VAr-hours Imported Q1 phase C | |
TotVArhImpQ2 | acc32 | varh | Total VAr-hours Imported Q2 | Total Reactive Power Imported Quadrant 2 |
TotVArhImpQ2PhA | acc32 | varh | Total VAr-hours Imported Q2 phase A | |
TotVArhImpQ2PhB | acc32 | varh | Total VAr-hours Imported Q2 phase B | |
TotVArhImpQ2PhC | acc32 | varh | Total VAr-hours Imported Q2 phase C | |
TotVArhExpQ3 | acc32 | varh | Total VAr-hours Exported Q3 | Total Reactive Power Exported Quadrant 3 |
TotVArhExpQ3PhA | acc32 | varh | Total VAr-hours Exported Q3 phase A | |
TotVArhExpQ3PhB | acc32 | varh | Total VAr-hours Exported Q3 phase B | |
TotVArhExpQ3PhC | acc32 | varh | Total VAr-hours Exported Q3 phase C | |
TotVArhExpQ4 | acc32 | varh | Total VAr-hours Exported Q4 | Total Reactive Power Exported Quadrant 4 |
TotVArhExpQ4PhA | acc32 | varh | Total VAr-hours Exported Q4 Imported phase A | |
TotVArhExpQ4PhB | acc32 | varh | Total VAr-hours Exported Q4 Imported phase B | |
TotVArhExpQ4PhC | acc32 | varh | Total VAr-hours Exported Q4 Imported phase C | |
Evt | bitfield32 | Events | Meter Event Flags |
Value names:
Evt(bitfield32): bit 2M_EVENT_Power_Failure, bit 3M_EVENT_Under_Voltage, bit 4M_EVENT_Low_PF, bit 5M_EVENT_Over_Current, bit 6M_EVENT_Over_Voltage, bit 7M_EVENT_Missing_Sensor, bit 8M_EVENT_Reserved1, bit 9M_EVENT_Reserved2, bit 10M_EVENT_Reserved3, bit 11M_EVENT_Reserved4, bit 12M_EVENT_Reserved5, bit 13M_EVENT_Reserved6, bit 14M_EVENT_Reserved7, bit 15M_EVENT_Reserved8, bit 16M_EVENT_OEM01, bit 17M_EVENT_OEM02, bit 18M_EVENT_OEM03, bit 19M_EVENT_OEM04, bit 20M_EVENT_OEM05, bit 21M_EVENT_OEM06, bit 22M_EVENT_OEM07, bit 23M_EVENT_OEM08, bit 24M_EVENT_OEM09, bit 25M_EVENT_OEM10, bit 26M_EVENT_OEM11, bit 27M_EVENT_OEM12, bit 28M_EVENT_OEM13, bit 29M_EVENT_OEM14, bit 30M_EVENT_OEM15
Model 203: wye-connect three phase (abcn) meter
Name in records: ac_meter_abcn.
| Point | Type | Units | Label | Description |
|---|---|---|---|---|
A | int16 | A | Amps | Total AC Current |
AphA | int16 | A | Amps PhaseA | Phase A Current |
AphB | int16 | A | Amps PhaseB | Phase B Current |
AphC | int16 | A | Amps PhaseC | Phase C Current |
PhV | int16 | V | Voltage LN | Line to Neutral AC Voltage (average of active phases) |
PhVphA | int16 | V | Phase Voltage AN | Phase Voltage AN |
PhVphB | int16 | V | Phase Voltage BN | Phase Voltage BN |
PhVphC | int16 | V | Phase Voltage CN | Phase Voltage CN |
PPV | int16 | V | Voltage LL | Line to Line AC Voltage (average of active phases) |
PhVphAB | int16 | V | Phase Voltage AB | Phase Voltage AB |
PhVphBC | int16 | V | Phase Voltage BC | Phase Voltage BC |
PhVphCA | int16 | V | Phase Voltage CA | Phase Voltage CA |
Hz | int16 | Hz | Hz | Frequency |
W | int16 | W | Watts | Total Real Power |
WphA | int16 | W | Watts phase A | |
WphB | int16 | W | Watts phase B | |
WphC | int16 | W | Watts phase C | |
VA | int16 | VA | VA | AC Apparent Power |
VAphA | int16 | VA | VA phase A | |
VAphB | int16 | VA | VA phase B | |
VAphC | int16 | VA | VA phase C | |
VAR | int16 | var | VAR | Reactive Power |
VARphA | int16 | var | VAR phase A | |
VARphB | int16 | var | VAR phase B | |
VARphC | int16 | var | VAR phase C | |
PF | int16 | Pct | PF | Power Factor |
PFphA | int16 | Pct | PF phase A | |
PFphB | int16 | Pct | PF phase B | |
PFphC | int16 | Pct | PF phase C | |
TotWhExp | acc32 | Wh | Total Watt-hours Exported | Total Real Energy Exported |
TotWhExpPhA | acc32 | Wh | Total Watt-hours Exported phase A | |
TotWhExpPhB | acc32 | Wh | Total Watt-hours Exported phase B | |
TotWhExpPhC | acc32 | Wh | Total Watt-hours Exported phase C | |
TotWhImp | acc32 | Wh | Total Watt-hours Imported | Total Real Energy Imported |
TotWhImpPhA | acc32 | Wh | Total Watt-hours Imported phase A | |
TotWhImpPhB | acc32 | Wh | Total Watt-hours Imported phase B | |
TotWhImpPhC | acc32 | Wh | Total Watt-hours Imported phase C | |
TotVAhExp | acc32 | VAh | Total VA-hours Exported | Total Apparent Energy Exported |
TotVAhExpPhA | acc32 | VAh | Total VA-hours Exported phase A | |
TotVAhExpPhB | acc32 | VAh | Total VA-hours Exported phase B | |
TotVAhExpPhC | acc32 | VAh | Total VA-hours Exported phase C | |
TotVAhImp | acc32 | VAh | Total VA-hours Imported | Total Apparent Energy Imported |
TotVAhImpPhA | acc32 | VAh | Total VA-hours Imported phase A | |
TotVAhImpPhB | acc32 | VAh | Total VA-hours Imported phase B | |
TotVAhImpPhC | acc32 | VAh | Total VA-hours Imported phase C | |
TotVArhImpQ1 | acc32 | varh | Total VAR-hours Imported Q1 | Total Reactive Energy Imported Quadrant 1 |
TotVArhImpQ1PhA | acc32 | varh | Total VAr-hours Imported Q1 phase A | |
TotVArhImpQ1PhB | acc32 | varh | Total VAr-hours Imported Q1 phase B | |
TotVArhImpQ1PhC | acc32 | varh | Total VAr-hours Imported Q1 phase C | |
TotVArhImpQ2 | acc32 | varh | Total VAr-hours Imported Q2 | Total Reactive Power Imported Quadrant 2 |
TotVArhImpQ2PhA | acc32 | varh | Total VAr-hours Imported Q2 phase A | |
TotVArhImpQ2PhB | acc32 | varh | Total VAr-hours Imported Q2 phase B | |
TotVArhImpQ2PhC | acc32 | varh | Total VAr-hours Imported Q2 phase C | |
TotVArhExpQ3 | acc32 | varh | Total VAr-hours Exported Q3 | Total Reactive Power Exported Quadrant 3 |
TotVArhExpQ3PhA | acc32 | varh | Total VAr-hours Exported Q3 phase A | |
TotVArhExpQ3PhB | acc32 | varh | Total VAr-hours Exported Q3 phase B | |
TotVArhExpQ3PhC | acc32 | varh | Total VAr-hours Exported Q3 phase C | |
TotVArhExpQ4 | acc32 | varh | Total VAr-hours Exported Q4 | Total Reactive Power Exported Quadrant 4 |
TotVArhExpQ4PhA | acc32 | varh | Total VAr-hours Exported Q4 Imported phase A | |
TotVArhExpQ4PhB | acc32 | varh | Total VAr-hours Exported Q4 Imported phase B | |
TotVArhExpQ4PhC | acc32 | varh | Total VAr-hours Exported Q4 Imported phase C | |
Evt | bitfield32 | Events | Meter Event Flags |
Value names:
Evt(bitfield32): bit 2M_EVENT_Power_Failure, bit 3M_EVENT_Under_Voltage, bit 4M_EVENT_Low_PF, bit 5M_EVENT_Over_Current, bit 6M_EVENT_Over_Voltage, bit 7M_EVENT_Missing_Sensor, bit 8M_EVENT_Reserved1, bit 9M_EVENT_Reserved2, bit 10M_EVENT_Reserved3, bit 11M_EVENT_Reserved4, bit 12M_EVENT_Reserved5, bit 13M_EVENT_Reserved6, bit 14M_EVENT_Reserved7, bit 15M_EVENT_Reserved8, bit 16M_EVENT_OEM01, bit 17M_EVENT_OEM02, bit 18M_EVENT_OEM03, bit 19M_EVENT_OEM04, bit 20M_EVENT_OEM05, bit 21M_EVENT_OEM06, bit 22M_EVENT_OEM07, bit 23M_EVENT_OEM08, bit 24M_EVENT_OEM09, bit 25M_EVENT_OEM10, bit 26M_EVENT_OEM11, bit 27M_EVENT_OEM12, bit 28M_EVENT_OEM13, bit 29M_EVENT_OEM14, bit 30M_EVENT_OEM15
Model 204: delta-connect three phase (abc) meter
Name in records: ac_meter_abc.
| Point | Type | Units | Label | Description |
|---|---|---|---|---|
A | int16 | A | Amps | Total AC Current |
AphA | int16 | A | Amps PhaseA | Phase A Current |
AphB | int16 | A | Amps PhaseB | Phase B Current |
AphC | int16 | A | Amps PhaseC | Phase C Current |
PhV | int16 | V | Voltage LN | Line to Neutral AC Voltage (average of active phases) |
PhVphA | int16 | V | Phase Voltage AN | Phase Voltage AN |
PhVphB | int16 | V | Phase Voltage BN | Phase Voltage BN |
PhVphC | int16 | V | Phase Voltage CN | Phase Voltage CN |
PPV | int16 | V | Voltage LL | Line to Line AC Voltage (average of active phases) |
PhVphAB | int16 | V | Phase Voltage AB | Phase Voltage AB |
PhVphBC | int16 | V | Phase Voltage BC | Phase Voltage BC |
PhVphCA | int16 | V | Phase Voltage CA | Phase Voltage CA |
Hz | int16 | Hz | Hz | Frequency |
W | int16 | W | Watts | Total Real Power |
WphA | int16 | W | Watts phase A | |
WphB | int16 | W | Watts phase B | |
WphC | int16 | W | Watts phase C | |
VA | int16 | VA | VA | AC Apparent Power |
VAphA | int16 | VA | VA phase A | |
VAphB | int16 | VA | VA phase B | |
VAphC | int16 | VA | VA phase C | |
VAR | int16 | var | VAR | Reactive Power |
VARphA | int16 | var | VAR phase A | |
VARphB | int16 | var | VAR phase B | |
VARphC | int16 | var | VAR phase C | |
PF | int16 | Pct | PF | Power Factor |
PFphA | int16 | Pct | PF phase A | |
PFphB | int16 | Pct | PF phase B | |
PFphC | int16 | Pct | PF phase C | |
TotWhExp | acc32 | Wh | Total Watt-hours Exported | Total Real Energy Exported |
TotWhExpPhA | acc32 | Wh | Total Watt-hours Exported phase A | |
TotWhExpPhB | acc32 | Wh | Total Watt-hours Exported phase B | |
TotWhExpPhC | acc32 | Wh | Total Watt-hours Exported phase C | |
TotWhImp | acc32 | Wh | Total Watt-hours Imported | Total Real Energy Imported |
TotWhImpPhA | acc32 | Wh | Total Watt-hours Imported phase A | |
TotWhImpPhB | acc32 | Wh | Total Watt-hours Imported phase B | |
TotWhImpPhC | acc32 | Wh | Total Watt-hours Imported phase C | |
TotVAhExp | acc32 | VAh | Total VA-hours Exported | Total Apparent Energy Exported |
TotVAhExpPhA | acc32 | VAh | Total VA-hours Exported phase A | |
TotVAhExpPhB | acc32 | VAh | Total VA-hours Exported phase B | |
TotVAhExpPhC | acc32 | VAh | Total VA-hours Exported phase C | |
TotVAhImp | acc32 | VAh | Total VA-hours Imported | Total Apparent Energy Imported |
TotVAhImpPhA | acc32 | VAh | Total VA-hours Imported phase A | |
TotVAhImpPhB | acc32 | VAh | Total VA-hours Imported phase B | |
TotVAhImpPhC | acc32 | VAh | Total VA-hours Imported phase C | |
TotVArhImpQ1 | acc32 | varh | Total VAR-hours Imported Q1 | Total Reactive Energy Imported Quadrant 1 |
TotVArhImpQ1PhA | acc32 | varh | Total VAr-hours Imported Q1 phase A | |
TotVArhImpQ1PhB | acc32 | varh | Total VAr-hours Imported Q1 phase B | |
TotVArhImpQ1PhC | acc32 | varh | Total VAr-hours Imported Q1 phase C | |
TotVArhImpQ2 | acc32 | varh | Total VAr-hours Imported Q2 | Total Reactive Power Imported Quadrant 2 |
TotVArhImpQ2PhA | acc32 | varh | Total VAr-hours Imported Q2 phase A | |
TotVArhImpQ2PhB | acc32 | varh | Total VAr-hours Imported Q2 phase B | |
TotVArhImpQ2PhC | acc32 | varh | Total VAr-hours Imported Q2 phase C | |
TotVArhExpQ3 | acc32 | varh | Total VAr-hours Exported Q3 | Total Reactive Power Exported Quadrant 3 |
TotVArhExpQ3PhA | acc32 | varh | Total VAr-hours Exported Q3 phase A | |
TotVArhExpQ3PhB | acc32 | varh | Total VAr-hours Exported Q3 phase B | |
TotVArhExpQ3PhC | acc32 | varh | Total VAr-hours Exported Q3 phase C | |
TotVArhExpQ4 | acc32 | varh | Total VAr-hours Exported Q4 | Total Reactive Power Exported Quadrant 4 |
TotVArhExpQ4PhA | acc32 | varh | Total VAr-hours Exported Q4 Imported phase A | |
TotVArhExpQ4PhB | acc32 | varh | Total VAr-hours Exported Q4 Imported phase B | |
TotVArhExpQ4PhC | acc32 | varh | Total VAr-hours Exported Q4 Imported phase C | |
Evt | bitfield32 | Events | Meter Event Flags |
Value names:
Evt(bitfield32): bit 2M_EVENT_Power_Failure, bit 3M_EVENT_Under_Voltage, bit 4M_EVENT_Low_PF, bit 5M_EVENT_Over_Current, bit 6M_EVENT_Over_Voltage, bit 7M_EVENT_Missing_Sensor, bit 8M_EVENT_Reserved1, bit 9M_EVENT_Reserved2, bit 10M_EVENT_Reserved3, bit 11M_EVENT_Reserved4, bit 12M_EVENT_Reserved5, bit 13M_EVENT_Reserved6, bit 14M_EVENT_Reserved7, bit 15M_EVENT_Reserved8, bit 16M_EVENT_OEM01, bit 17M_EVENT_OEM02, bit 18M_EVENT_OEM03, bit 19M_EVENT_OEM04, bit 20M_EVENT_OEM05, bit 21M_EVENT_OEM06, bit 22M_EVENT_OEM07, bit 23M_EVENT_OEM08, bit 24M_EVENT_OEM09, bit 25M_EVENT_OEM10, bit 26M_EVENT_OEM11, bit 27M_EVENT_OEM12, bit 28M_EVENT_OEM13, bit 29M_EVENT_OEM14, bit 30M_EVENT_OEM15
Model 211: single phase (AN or AB) meter
Name in records: ac_meter_an_or_ab_float.
| Point | Type | Units | Label | Description |
|---|---|---|---|---|
A | float32 | A | Amps | Total AC Current |
AphA | float32 | A | Amps PhaseA | Phase A Current |
AphB | float32 | A | Amps PhaseB | Phase B Current |
AphC | float32 | A | Amps PhaseC | Phase C Current |
PhV | float32 | V | Voltage LN | Line to Neutral AC Voltage (average of active phases) |
PhVphA | float32 | V | Phase Voltage AN | Phase Voltage AN |
PhVphB | float32 | V | Phase Voltage BN | Phase Voltage BN |
PhVphC | float32 | V | Phase Voltage CN | Phase Voltage CN |
PPV | float32 | V | Voltage LL | Line to Line AC Voltage (average of active phases) |
PPVphAB | float32 | V | Phase Voltage AB | Phase Voltage AB |
PPVphBC | float32 | V | Phase Voltage BC | Phase Voltage BC |
PPVphCA | float32 | V | Phase Voltage CA | Phase Voltage CA |
Hz | float32 | Hz | Hz | Frequency |
W | float32 | W | Watts | Total Real Power |
WphA | float32 | W | Watts phase A | |
WphB | float32 | W | Watts phase B | |
WphC | float32 | W | Watts phase C | |
VA | float32 | VA | VA | AC Apparent Power |
VAphA | float32 | VA | VA phase A | |
VAphB | float32 | VA | VA phase B | |
VAphC | float32 | VA | VA phase C | |
VAR | float32 | var | VAR | Reactive Power |
VARphA | float32 | var | VAR phase A | |
VARphB | float32 | var | VAR phase B | |
VARphC | float32 | var | VAR phase C | |
PF | float32 | PF | PF | Power Factor |
PFphA | float32 | PF | PF phase A | |
PFphB | float32 | PF | PF phase B | |
PFphC | float32 | PF | PF phase C | |
TotWhExp | float32 | Wh | Total Watt-hours Exported | Total Real Energy Exported |
TotWhExpPhA | float32 | Wh | Total Watt-hours Exported phase A | |
TotWhExpPhB | float32 | Wh | Total Watt-hours Exported phase B | |
TotWhExpPhC | float32 | Wh | Total Watt-hours Exported phase C | |
TotWhImp | float32 | Wh | Total Watt-hours Imported | Total Real Energy Imported |
TotWhImpPhA | float32 | Wh | Total Watt-hours Imported phase A | |
TotWhImpPhB | float32 | Wh | Total Watt-hours Imported phase B | |
TotWhImpPhC | float32 | Wh | Total Watt-hours Imported phase C | |
TotVAhExp | float32 | VAh | Total VA-hours Exported | Total Apparent Energy Exported |
TotVAhExpPhA | float32 | VAh | Total VA-hours Exported phase A | |
TotVAhExpPhB | float32 | VAh | Total VA-hours Exported phase B | |
TotVAhExpPhC | float32 | VAh | Total VA-hours Exported phase C | |
TotVAhImp | float32 | VAh | Total VA-hours Imported | Total Apparent Energy Imported |
TotVAhImpPhA | float32 | VAh | Total VA-hours Imported phase A | |
TotVAhImpPhB | float32 | VAh | Total VA-hours Imported phase B | |
TotVAhImpPhC | float32 | VAh | Total VA-hours Imported phase C | |
TotVArhImpQ1 | float32 | varh | Total VAR-hours Imported Q1 | Total Reactive Energy Imported Quadrant 1 |
TotVArhImpQ1phA | float32 | varh | Total VAr-hours Imported Q1 phase A | |
TotVArhImpQ1phB | float32 | varh | Total VAr-hours Imported Q1 phase B | |
TotVArhImpQ1phC | float32 | varh | Total VAr-hours Imported Q1 phase C | |
TotVArhImpQ2 | float32 | varh | Total VAr-hours Imported Q2 | Total Reactive Power Imported Quadrant 2 |
TotVArhImpQ2phA | float32 | varh | Total VAr-hours Imported Q2 phase A | |
TotVArhImpQ2phB | float32 | varh | Total VAr-hours Imported Q2 phase B | |
TotVArhImpQ2phC | float32 | varh | Total VAr-hours Imported Q2 phase C | |
TotVArhExpQ3 | float32 | varh | Total VAr-hours Exported Q3 | Total Reactive Power Exported Quadrant 3 |
TotVArhExpQ3phA | float32 | varh | Total VAr-hours Exported Q3 phase A | |
TotVArhExpQ3phB | float32 | varh | Total VAr-hours Exported Q3 phase B | |
TotVArhExpQ3phC | float32 | varh | Total VAr-hours Exported Q3 phase C | |
TotVArhExpQ4 | float32 | varh | Total VAr-hours Exported Q4 | Total Reactive Power Exported Quadrant 4 |
TotVArhExpQ4phA | float32 | varh | Total VAr-hours Exported Q4 Imported phase A | |
TotVArhExpQ4phB | float32 | varh | Total VAr-hours Exported Q4 Imported phase B | |
TotVArhExpQ4phC | float32 | varh | Total VAr-hours Exported Q4 Imported phase C | |
Evt | bitfield32 | Events | Meter Event Flags |
Value names:
Evt(bitfield32): bit 2M_EVENT_Power_Failure, bit 3M_EVENT_Under_Voltage, bit 4M_EVENT_Low_PF, bit 5M_EVENT_Over_Current, bit 6M_EVENT_Over_Voltage, bit 7M_EVENT_Missing_Sensor, bit 8M_EVENT_Reserved1, bit 9M_EVENT_Reserved2, bit 10M_EVENT_Reserved3, bit 11M_EVENT_Reserved4, bit 12M_EVENT_Reserved5, bit 13M_EVENT_Reserved6, bit 14M_EVENT_Reserved7, bit 15M_EVENT_Reserved8, bit 16M_EVENT_OEM01, bit 17M_EVENT_OEM02, bit 18M_EVENT_OEM03, bit 19M_EVENT_OEM04, bit 20M_EVENT_OEM05, bit 21M_EVENT_OEM06, bit 22M_EVENT_OEM07, bit 23M_EVENT_OEM08, bit 24M_EVENT_OEM09, bit 25M_EVENT_OEM10, bit 26M_EVENT_OEM11, bit 27M_EVENT_OEM12, bit 28M_EVENT_OEM13, bit 29M_EVENT_OEM14, bit 30M_EVENT_OEM15
Model 212: split single phase (ABN) meter
Name in records: ac_meter_abn_float.
| Point | Type | Units | Label | Description |
|---|---|---|---|---|
A | float32 | A | Amps | Total AC Current |
AphA | float32 | A | Amps PhaseA | Phase A Current |
AphB | float32 | A | Amps PhaseB | Phase B Current |
AphC | float32 | A | Amps PhaseC | Phase C Current |
PhV | float32 | V | Voltage LN | Line to Neutral AC Voltage (average of active phases) |
PhVphA | float32 | V | Phase Voltage AN | Phase Voltage AN |
PhVphB | float32 | V | Phase Voltage BN | Phase Voltage BN |
PhVphC | float32 | V | Phase Voltage CN | Phase Voltage CN |
PPV | float32 | V | Voltage LL | Line to Line AC Voltage (average of active phases) |
PPVphAB | float32 | V | Phase Voltage AB | Phase Voltage AB |
PPVphBC | float32 | V | Phase Voltage BC | Phase Voltage BC |
PPVphCA | float32 | V | Phase Voltage CA | Phase Voltage CA |
Hz | float32 | Hz | Hz | Frequency |
W | float32 | W | Watts | Total Real Power |
WphA | float32 | W | Watts phase A | |
WphB | float32 | W | Watts phase B | |
WphC | float32 | W | Watts phase C | |
VA | float32 | VA | VA | AC Apparent Power |
VAphA | float32 | VA | VA phase A | |
VAphB | float32 | VA | VA phase B | |
VAphC | float32 | VA | VA phase C | |
VAR | float32 | var | VAR | Reactive Power |
VARphA | float32 | var | VAR phase A | |
VARphB | float32 | var | VAR phase B | |
VARphC | float32 | var | VAR phase C | |
PF | float32 | PF | PF | Power Factor |
PFphA | float32 | PF | PF phase A | |
PFphB | float32 | PF | PF phase B | |
PFphC | float32 | PF | PF phase C | |
TotWhExp | float32 | Wh | Total Watt-hours Exported | Total Real Energy Exported |
TotWhExpPhA | float32 | Wh | Total Watt-hours Exported phase A | |
TotWhExpPhB | float32 | Wh | Total Watt-hours Exported phase B | |
TotWhExpPhC | float32 | Wh | Total Watt-hours Exported phase C | |
TotWhImp | float32 | Wh | Total Watt-hours Imported | Total Real Energy Imported |
TotWhImpPhA | float32 | Wh | Total Watt-hours Imported phase A | |
TotWhImpPhB | float32 | Wh | Total Watt-hours Imported phase B | |
TotWhImpPhC | float32 | Wh | Total Watt-hours Imported phase C | |
TotVAhExp | float32 | VAh | Total VA-hours Exported | Total Apparent Energy Exported |
TotVAhExpPhA | float32 | VAh | Total VA-hours Exported phase A | |
TotVAhExpPhB | float32 | VAh | Total VA-hours Exported phase B | |
TotVAhExpPhC | float32 | VAh | Total VA-hours Exported phase C | |
TotVAhImp | float32 | VAh | Total VA-hours Imported | Total Apparent Energy Imported |
TotVAhImpPhA | float32 | VAh | Total VA-hours Imported phase A | |
TotVAhImpPhB | float32 | VAh | Total VA-hours Imported phase B | |
TotVAhImpPhC | float32 | VAh | Total VA-hours Imported phase C | |
TotVArhImpQ1 | float32 | varh | Total VAR-hours Imported Q1 | Total Reactive Energy Imported Quadrant 1 |
TotVArhImpQ1phA | float32 | varh | Total VAr-hours Imported Q1 phase A | |
TotVArhImpQ1phB | float32 | varh | Total VAr-hours Imported Q1 phase B | |
TotVArhImpQ1phC | float32 | varh | Total VAr-hours Imported Q1 phase C | |
TotVArhImpQ2 | float32 | varh | Total VAr-hours Imported Q2 | Total Reactive Power Imported Quadrant 2 |
TotVArhImpQ2phA | float32 | varh | Total VAr-hours Imported Q2 phase A | |
TotVArhImpQ2phB | float32 | varh | Total VAr-hours Imported Q2 phase B | |
TotVArhImpQ2phC | float32 | varh | Total VAr-hours Imported Q2 phase C | |
TotVArhExpQ3 | float32 | varh | Total VAr-hours Exported Q3 | Total Reactive Power Exported Quadrant 3 |
TotVArhExpQ3phA | float32 | varh | Total VAr-hours Exported Q3 phase A | |
TotVArhExpQ3phB | float32 | varh | Total VAr-hours Exported Q3 phase B | |
TotVArhExpQ3phC | float32 | varh | Total VAr-hours Exported Q3 phase C | |
TotVArhExpQ4 | float32 | varh | Total VAr-hours Exported Q4 | Total Reactive Power Exported Quadrant 4 |
TotVArhExpQ4phA | float32 | varh | Total VAr-hours Exported Q4 Imported phase A | |
TotVArhExpQ4phB | float32 | varh | Total VAr-hours Exported Q4 Imported phase B | |
TotVArhExpQ4phC | float32 | varh | Total VAr-hours Exported Q4 Imported phase C | |
Evt | bitfield32 | Events | Meter Event Flags |
Value names:
Evt(bitfield32): bit 2M_EVENT_Power_Failure, bit 3M_EVENT_Under_Voltage, bit 4M_EVENT_Low_PF, bit 5M_EVENT_Over_Current, bit 6M_EVENT_Over_Voltage, bit 7M_EVENT_Missing_Sensor, bit 8M_EVENT_Reserved1, bit 9M_EVENT_Reserved2, bit 10M_EVENT_Reserved3, bit 11M_EVENT_Reserved4, bit 12M_EVENT_Reserved5, bit 13M_EVENT_Reserved6, bit 14M_EVENT_Reserved7, bit 15M_EVENT_Reserved8, bit 16M_EVENT_OEM01, bit 17M_EVENT_OEM02, bit 18M_EVENT_OEM03, bit 19M_EVENT_OEM04, bit 20M_EVENT_OEM05, bit 21M_EVENT_OEM06, bit 22M_EVENT_OEM07, bit 23M_EVENT_OEM08, bit 24M_EVENT_OEM09, bit 25M_EVENT_OEM10, bit 26M_EVENT_OEM11, bit 27M_EVENT_OEM12, bit 28M_EVENT_OEM13, bit 29M_EVENT_OEM14, bit 30M_EVENT_OEM15
Model 213: wye-connect three phase (abcn) meter
Name in records: ac_meter_abcn_float.
| Point | Type | Units | Label | Description |
|---|---|---|---|---|
A | float32 | A | Amps | Total AC Current |
AphA | float32 | A | Amps PhaseA | Phase A Current |
AphB | float32 | A | Amps PhaseB | Phase B Current |
AphC | float32 | A | Amps PhaseC | Phase C Current |
PhV | float32 | V | Voltage LN | Line to Neutral AC Voltage (average of active phases) |
PhVphA | float32 | V | Phase Voltage AN | Phase Voltage AN |
PhVphB | float32 | V | Phase Voltage BN | Phase Voltage BN |
PhVphC | float32 | V | Phase Voltage CN | Phase Voltage CN |
PPV | float32 | V | Voltage LL | Line to Line AC Voltage (average of active phases) |
PPVphAB | float32 | V | Phase Voltage AB | Phase Voltage AB |
PPVphBC | float32 | V | Phase Voltage BC | Phase Voltage BC |
PPVphCA | float32 | V | Phase Voltage CA | Phase Voltage CA |
Hz | float32 | Hz | Hz | Frequency |
W | float32 | W | Watts | Total Real Power |
WphA | float32 | W | Watts phase A | |
WphB | float32 | W | Watts phase B | |
WphC | float32 | W | Watts phase C | |
VA | float32 | VA | VA | AC Apparent Power |
VAphA | float32 | VA | VA phase A | |
VAphB | float32 | VA | VA phase B | |
VAphC | float32 | VA | VA phase C | |
VAR | float32 | var | VAR | Reactive Power |
VARphA | float32 | var | VAR phase A | |
VARphB | float32 | var | VAR phase B | |
VARphC | float32 | var | VAR phase C | |
PF | float32 | PF | PF | Power Factor |
PFphA | float32 | PF | PF phase A | |
PFphB | float32 | PF | PF phase B | |
PFphC | float32 | PF | PF phase C | |
TotWhExp | float32 | Wh | Total Watt-hours Exported | Total Real Energy Exported |
TotWhExpPhA | float32 | Wh | Total Watt-hours Exported phase A | |
TotWhExpPhB | float32 | Wh | Total Watt-hours Exported phase B | |
TotWhExpPhC | float32 | Wh | Total Watt-hours Exported phase C | |
TotWhImp | float32 | Wh | Total Watt-hours Imported | Total Real Energy Imported |
TotWhImpPhA | float32 | Wh | Total Watt-hours Imported phase A | |
TotWhImpPhB | float32 | Wh | Total Watt-hours Imported phase B | |
TotWhImpPhC | float32 | Wh | Total Watt-hours Imported phase C | |
TotVAhExp | float32 | VAh | Total VA-hours Exported | Total Apparent Energy Exported |
TotVAhExpPhA | float32 | VAh | Total VA-hours Exported phase A | |
TotVAhExpPhB | float32 | VAh | Total VA-hours Exported phase B | |
TotVAhExpPhC | float32 | VAh | Total VA-hours Exported phase C | |
TotVAhImp | float32 | VAh | Total VA-hours Imported | Total Apparent Energy Imported |
TotVAhImpPhA | float32 | VAh | Total VA-hours Imported phase A | |
TotVAhImpPhB | float32 | VAh | Total VA-hours Imported phase B | |
TotVAhImpPhC | float32 | VAh | Total VA-hours Imported phase C | |
TotVArhImpQ1 | float32 | varh | Total VAR-hours Imported Q1 | Total Reactive Energy Imported Quadrant 1 |
TotVArhImpQ1phA | float32 | varh | Total VAr-hours Imported Q1 phase A | |
TotVArhImpQ1phB | float32 | varh | Total VAr-hours Imported Q1 phase B | |
TotVArhImpQ1phC | float32 | varh | Total VAr-hours Imported Q1 phase C | |
TotVArhImpQ2 | float32 | varh | Total VAr-hours Imported Q2 | Total Reactive Power Imported Quadrant 2 |
TotVArhImpQ2phA | float32 | varh | Total VAr-hours Imported Q2 phase A | |
TotVArhImpQ2phB | float32 | varh | Total VAr-hours Imported Q2 phase B | |
TotVArhImpQ2phC | float32 | varh | Total VAr-hours Imported Q2 phase C | |
TotVArhExpQ3 | float32 | varh | Total VAr-hours Exported Q3 | Total Reactive Power Exported Quadrant 3 |
TotVArhExpQ3phA | float32 | varh | Total VAr-hours Exported Q3 phase A | |
TotVArhExpQ3phB | float32 | varh | Total VAr-hours Exported Q3 phase B | |
TotVArhExpQ3phC | float32 | varh | Total VAr-hours Exported Q3 phase C | |
TotVArhExpQ4 | float32 | varh | Total VAr-hours Exported Q4 | Total Reactive Power Exported Quadrant 4 |
TotVArhExpQ4phA | float32 | varh | Total VAr-hours Exported Q4 Imported phase A | |
TotVArhExpQ4phB | float32 | varh | Total VAr-hours Exported Q4 Imported phase B | |
TotVArhExpQ4phC | float32 | varh | Total VAr-hours Exported Q4 Imported phase C | |
Evt | bitfield32 | Events | Meter Event Flags |
Value names:
Evt(bitfield32): bit 2M_EVENT_Power_Failure, bit 3M_EVENT_Under_Voltage, bit 4M_EVENT_Low_PF, bit 5M_EVENT_Over_Current, bit 6M_EVENT_Over_Voltage, bit 7M_EVENT_Missing_Sensor, bit 8M_EVENT_Reserved1, bit 9M_EVENT_Reserved2, bit 10M_EVENT_Reserved3, bit 11M_EVENT_Reserved4, bit 12M_EVENT_Reserved5, bit 13M_EVENT_Reserved6, bit 14M_EVENT_Reserved7, bit 15M_EVENT_Reserved8, bit 16M_EVENT_OEM01, bit 17M_EVENT_OEM02, bit 18M_EVENT_OEM03, bit 19M_EVENT_OEM04, bit 20M_EVENT_OEM05, bit 21M_EVENT_OEM06, bit 22M_EVENT_OEM07, bit 23M_EVENT_OEM08, bit 24M_EVENT_OEM09, bit 25M_EVENT_OEM10, bit 26M_EVENT_OEM11, bit 27M_EVENT_OEM12, bit 28M_EVENT_OEM13, bit 29M_EVENT_OEM14, bit 30M_EVENT_OEM15
Model 214: delta-connect three phase (abc) meter
Name in records: ac_meter_abc_float.
| Point | Type | Units | Label | Description |
|---|---|---|---|---|
A | float32 | A | Amps | Total AC Current |
AphA | float32 | A | Amps PhaseA | Phase A Current |
AphB | float32 | A | Amps PhaseB | Phase B Current |
AphC | float32 | A | Amps PhaseC | Phase C Current |
PhV | float32 | V | Voltage LN | Line to Neutral AC Voltage (average of active phases) |
PhVphA | float32 | V | Phase Voltage AN | Phase Voltage AN |
PhVphB | float32 | V | Phase Voltage BN | Phase Voltage BN |
PhVphC | float32 | V | Phase Voltage CN | Phase Voltage CN |
PPV | float32 | V | Voltage LL | Line to Line AC Voltage (average of active phases) |
PPVphAB | float32 | V | Phase Voltage AB | Phase Voltage AB |
PPVphBC | float32 | V | Phase Voltage BC | Phase Voltage BC |
PPVphCA | float32 | V | Phase Voltage CA | Phase Voltage CA |
Hz | float32 | Hz | Hz | Frequency |
W | float32 | W | Watts | Total Real Power |
WphA | float32 | W | Watts phase A | |
WphB | float32 | W | Watts phase B | |
WphC | float32 | W | Watts phase C | |
VA | float32 | VA | VA | AC Apparent Power |
VAphA | float32 | VA | VA phase A | |
VAphB | float32 | VA | VA phase B | |
VAphC | float32 | VA | VA phase C | |
VAR | float32 | var | VAR | Reactive Power |
VARphA | float32 | var | VAR phase A | |
VARphB | float32 | var | VAR phase B | |
VARphC | float32 | var | VAR phase C | |
PF | float32 | PF | PF | Power Factor |
PFphA | float32 | PF | PF phase A | |
PFphB | float32 | PF | PF phase B | |
PFphC | float32 | PF | PF phase C | |
TotWhExp | float32 | Wh | Total Watt-hours Exported | Total Real Energy Exported |
TotWhExpPhA | float32 | Wh | Total Watt-hours Exported phase A | |
TotWhExpPhB | float32 | Wh | Total Watt-hours Exported phase B | |
TotWhExpPhC | float32 | Wh | Total Watt-hours Exported phase C | |
TotWhImp | float32 | Wh | Total Watt-hours Imported | Total Real Energy Imported |
TotWhImpPhA | float32 | Wh | Total Watt-hours Imported phase A | |
TotWhImpPhB | float32 | Wh | Total Watt-hours Imported phase B | |
TotWhImpPhC | float32 | Wh | Total Watt-hours Imported phase C | |
TotVAhExp | float32 | VAh | Total VA-hours Exported | Total Apparent Energy Exported |
TotVAhExpPhA | float32 | VAh | Total VA-hours Exported phase A | |
TotVAhExpPhB | float32 | VAh | Total VA-hours Exported phase B | |
TotVAhExpPhC | float32 | VAh | Total VA-hours Exported phase C | |
TotVAhImp | float32 | VAh | Total VA-hours Imported | Total Apparent Energy Imported |
TotVAhImpPhA | float32 | VAh | Total VA-hours Imported phase A | |
TotVAhImpPhB | float32 | VAh | Total VA-hours Imported phase B | |
TotVAhImpPhC | float32 | VAh | Total VA-hours Imported phase C | |
TotVArhImpQ1 | float32 | varh | Total VAR-hours Imported Q1 | Total Reactive Energy Imported Quadrant 1 |
TotVArhImpQ1phA | float32 | varh | Total VAr-hours Imported Q1 phase A | |
TotVArhImpQ1phB | float32 | varh | Total VAr-hours Imported Q1 phase B | |
TotVArhImpQ1phC | float32 | varh | Total VAr-hours Imported Q1 phase C | |
TotVArhImpQ2 | float32 | varh | Total VAr-hours Imported Q2 | Total Reactive Power Imported Quadrant 2 |
TotVArhImpQ2phA | float32 | varh | Total VAr-hours Imported Q2 phase A | |
TotVArhImpQ2phB | float32 | varh | Total VAr-hours Imported Q2 phase B | |
TotVArhImpQ2phC | float32 | varh | Total VAr-hours Imported Q2 phase C | |
TotVArhExpQ3 | float32 | varh | Total VAr-hours Exported Q3 | Total Reactive Power Exported Quadrant 3 |
TotVArhExpQ3phA | float32 | varh | Total VAr-hours Exported Q3 phase A | |
TotVArhExpQ3phB | float32 | varh | Total VAr-hours Exported Q3 phase B | |
TotVArhExpQ3phC | float32 | varh | Total VAr-hours Exported Q3 phase C | |
TotVArhExpQ4 | float32 | varh | Total VAr-hours Exported Q4 | Total Reactive Power Exported Quadrant 4 |
TotVArhExpQ4phA | float32 | varh | Total VAr-hours Exported Q4 Imported phase A | |
TotVArhExpQ4phB | float32 | varh | Total VAr-hours Exported Q4 Imported phase B | |
TotVArhExpQ4phC | float32 | varh | Total VAr-hours Exported Q4 Imported phase C | |
Evt | bitfield32 | Events | Meter Event Flags |
Value names:
Evt(bitfield32): bit 2M_EVENT_Power_Failure, bit 3M_EVENT_Under_Voltage, bit 4M_EVENT_Low_PF, bit 5M_EVENT_Over_Current, bit 6M_EVENT_Over_Voltage, bit 7M_EVENT_Missing_Sensor, bit 8M_EVENT_Reserved1, bit 9M_EVENT_Reserved2, bit 10M_EVENT_Reserved3, bit 11M_EVENT_Reserved4, bit 12M_EVENT_Reserved5, bit 13M_EVENT_Reserved6, bit 14M_EVENT_Reserved7, bit 15M_EVENT_Reserved8, bit 16M_EVENT_OEM01, bit 17M_EVENT_OEM02, bit 18M_EVENT_OEM03, bit 19M_EVENT_OEM04, bit 20M_EVENT_OEM05, bit 21M_EVENT_OEM06, bit 22M_EVENT_OEM07, bit 23M_EVENT_OEM08, bit 24M_EVENT_OEM09, bit 25M_EVENT_OEM10, bit 26M_EVENT_OEM11, bit 27M_EVENT_OEM12, bit 28M_EVENT_OEM13, bit 29M_EVENT_OEM14, bit 30M_EVENT_OEM15
Model 220: Secure AC Meter Selected Readings
Name in records: ac_meter_secure.
Include this model for secure metering
| Point | Type | Units | Label | Description |
|---|---|---|---|---|
A | int16 | A | Amps | Total AC Current |
PhV | int16 | V | Voltage | Average phase or line voltage |
Hz | int16 | Hz | Hz | Frequency |
W | int16 | W | Watts | Total Real Power |
VA | int16 | VA | VA | AC Apparent Power |
VAR | int16 | var | VAR | Reactive Power |
PF | int16 | Pct | PF | Power Factor |
TotWhExp | acc32 | Wh | Total Watt-hours Exported | Total Real Energy Exported |
TotWhImp | acc32 | Wh | Total Watt-hours Imported | Total Real Energy Imported |
TotVAhExp | acc32 | VAh | Total VA-hours Exported | Total Apparent Energy Exported |
TotVAhImp | acc32 | VAh | Total VA-hours Imported | Total Apparent Energy Imported |
TotVArhImpQ1 | acc32 | varh | Total VAR-hours Imported Q1 | Total Reactive Energy Imported Quadrant 1 |
TotVArhImpQ2 | acc32 | varh | Total VAr-hours Imported Q2 | Total Reactive Power Imported Quadrant 2 |
TotVArhExpQ3 | acc32 | varh | Total VAr-hours Exported Q3 | Total Reactive Power Exported Quadrant 3 |
TotVArhExpQ4 | acc32 | varh | Total VAr-hours Exported Q4 | Total Reactive Power Exported Quadrant 4 |
Evt | bitfield32 | Events | Meter Event Flags | |
Ts | uint32 | Timestamp | Timestamp value is the number of seconds since January 1, 2000 | |
Ms | uint16 | Milliseconds | Millisecond counter 0-999 | |
Seq | uint16 | Sequence | Sequence number of request | |
Alg | enum16 | Algorithm | Algorithm used to compute the digital signature | |
N | uint16 | N | Number of registers comprising the digital signature. | |
repeating[*].DS | uint16 |
Value names:
Evt(bitfield32): bit 2Power_Failure, bit 3Under_Voltage, bit 4Low_PF, bit 5Over_Current, bit 6Over_Voltage, bit 7Missing_Sensor, bit 16OEM01, bit 17OEM02, bit 18OEM03, bit 19OEM04, bit 20OEM05, bit 21OEM06, bit 22OEM07, bit 23OEM08, bit 24OEM09, bit 25OEM10, bit 26OEM11, bit 27OEM12, bit 28OEM13, bit 29OEM14, bit 30OEM15Alg(enum16): 0NONE, 1AES-GMAC-64, 2ECC-256